Final inspections for larger occupancies and or multifamily building swill require a final inspection before a certificate of occupancy is issued. With slight variations, we will be looking at the following during the inspection process:
- Fire Alarm System up and running
- All detectors in common areas to be tested
- All sprinkler functions, tamper, and flow for each outlet, on each floor tested and reporting back to the fire alarm system
- Fire Department Connection (FDC) properly labeled and a Knox FDC cover in place
- All smoke and carbon monoxide detectors in each unit working properly and correctly spaced
- Fire Alarm System properly reporting to a communications center, if you are connecting to the municipal system we require a Warn AES Radio Box with eight zones programmed as follows:
- Alarm-General
- Trouble
- Supervisory (duct smokes, etc.)
- Water flow
- First and second-floor devices
- Third and fourth-floor devices
- Open
- Open
- Fire extinguishers mounted and properly tagged as inspected and working
- All keys and access cards working, including elevator keys
- All signage for the Fire Alarm Control Panel (FACP), electrical room, and sprinkler room are in place
- Plans box in the foyer (maybe)
- Puff tests on the kitchen suppression systems
- Building properly numbered on the outside
Every commercial occupancy or multi-family residential property consisting of three or more dwelling units are subject to an annual fire safety inspection, subsequent follow-up inspections, or inspection if and when a complaint is filed with the fire department regarding the safety of the building. It is the building owner’s responsibility to ensure the fire department has up to date contact information for all commercial or multifamily residential units with three dwellings or more (Chapter 40, Town of Maynard By-Laws).
To schedule an inspection, please fill out the form below.